Question (ID18): |
Lack of safe distance |
Answer: |
Embodied in, the gas station tanks, tankers and ventilation tube station outside the mouth and built structures from fire, do not meet the "vehicle refueling stations design and construction standards" (2006) in the table 4.0.4 items from the requirements. Mainly in three aspects, ① tanks, ventilation tube from the mouth and civilian buildings in the inadequate; ② the distance between the tanker and the lack of urban roads; ③ with overhead power lines and communication lines from the gas station's tanks, tankers above through. |
|
|
Question (ID17): |
Electrical lines, anti-static measures do not meet the requirements |
Answer: |
Part of the station's operating room lighting circuits are not required to use explosion-proof lighting, explosion-proof switch. Although some gas stations use explosion-proof light fixtures, but the cable laying and the first failure to explosion-proof wiring, resulting in loss of explosion proof electrical role. In the daily inspection also found that some gas stations in the unloading site is not set static grounding device or settings are not standardized. Most owners know they should set up anti-static device, but understanding is not in place, there are chances. Tank driving process will produce a large number of static electricity, does not remove the static unloading, it is easy to produce sparks, explosion. |
|
|
Question (ID16): |
Tanker in a confined space |
Answer: |
Some small gas stations to protect the person in charge of the tanker, the tanker outside the installation of a glass envelope, so that daily oil, the volatile oil and gas it is easy to gather within the housing, prone to explosion. |
|
|